| Aplications | 
            : | 
            Emergency Power, Transformer Stations, Telecom, Solar | 
        
        
            | Standarts | 
            : | 
            IEC 896-1, DIN 40736, P1 | 
        
        
            Capacity Range in Ah 
             | 
            : | 
            200 - 3.000 | 
        
        
            Nominal Voltage Range 
             | 
            : | 
            2V | 
        
        
            Container Material 
             | 
            : | 
            SAN, Clear | 
        
        
            GRID ALLOY 
             | 
             
             | 
              | 
        
        
            | Pozitive | 
            : | 
            Pb+<2%Sb | 
        
        
            Negative 
             | 
            : | 
            Pb+<2%Sb | 
        
        
            Pozitive Plate 
             | 
            : | 
            Tubular | 
        
        
            Negative Plate 
             | 
            : | 
            Grid | 
        
        
            Electrolyte 
             | 
            : | 
            H2SO4, Liquid | 
        
        
            Connector Design 
             | 
            : | 
            Full Insulated Bolted Connector | 
        
        
            Current Behaviour(1-4) 
             | 
            : | 
            1 | 
        
        
            Battery Life (in year) 
             | 
            : | 
            20 | 
        
        
            Deisgn Life to(in year) 
             | 
            : | 
            1500 | 
        
        
            CHARGING VOLTAGE IN V/Cell 
             | 
            : | 
              | 
        
        
            Fload Charge 
             | 
            : | 
            2.23 | 
        
        
            Boost Charge 
             | 
            : | 
            2.4 | 
        
        
            Float Charging Current/100 Ah Nominal 
            (20oC, Ufloat=2.23 / 2.25 V /Cell) 
             | 
            : | 
            20-50 mA | 
        
        
            Position Independent Operation Possible 
             | 
            : | 
            No | 
        
        
            Water Reffilling Intervals in Year in Permanent 
            Float Charging/With Aqua Gen 
             | 
            : | 
            >3 / Not Necessary | 
        
        
            Self Discharge of Nominal Capacity at 20oC 
             | 
            : | 
            ~3% | 
        
        
            | Operating Temperature Range (20 oC) | 
            : | 
            (-20/+40) | 
        
        
            Ventilation Requirement 
             | 
            : | 
            with Aqua-Gen Similar to VRLA | 
        
        
            Storage Time at 20 oC Before Refresing Charge 
             | 
            : | 
            3 Months |